HAWK-I2-MIB DEFINITIONS ::= BEGIN


IMPORTS
	MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises, Unsigned32
		FROM SNMPv2-SMI
--	DisplayString, sysDescr, sysName
--		FROM RFC1213-MIB
--	MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP
--		FROM SNMPv2-CONF
	TEXTUAL-CONVENTION, RowStatus, TruthValue, MacAddress -- DateAndTime
		FROM SNMPv2-TC
	InetAddress, InetAddressType
		FROM INET-ADDRESS-MIB 
	;

hawki2MIB MODULE-IDENTITY
       LAST-UPDATED "200606271200Z"  -- 27 June 2006
       ORGANIZATION "Sinetica Corporation"
       CONTACT-INFO "Development Department

                     Sinetica Corporation Ltd.
                     Willow House
                     Llancayo Court
                     Usk
                     Monmouthshire
                     NP15 1HY
                     U.K.

                     Tel: +44 (0)871 226 5679
                     Fax: +44 (0)845 456 3562
                     Web: www.sinetica.co.uk
                     E-mail: info@sinetica.co.uk"
       DESCRIPTION
               "The MIB module for the Sinetica Hawk-i2."
       REVISION "200606271200Z"  -- 27 June 2006
       DESCRIPTION
               "Name change and new objects added"
       REVISION "200603071200Z"  -- 07 March 2006
       DESCRIPTION
               "First issue"
        ::= { sinetica 24 }

DisplayString ::= OCTET STRING

ContactState ::= TEXTUAL-CONVENTION
    STATUS       current
    DESCRIPTION
            "Represents the state of a set of contacts."
    SYNTAX       INTEGER { open(1), closed(2) }

InputContactState ::= TEXTUAL-CONVENTION
    STATUS       current
    DESCRIPTION
            "Represents the state of a set of input contacts."
    SYNTAX       INTEGER { open(1), closed(2), armed(3), triggered(4) }

RelayState ::= TEXTUAL-CONVENTION
    STATUS       current
    DESCRIPTION
            "Represents the energised state of a relay."
    SYNTAX       INTEGER { on(1), off(2) }       
    
OutputControlState ::= TEXTUAL-CONVENTION
    STATUS       current
    DESCRIPTION
            "Represents the control setiing for an output."
    SYNTAX       INTEGER { activate(1), deactivate(2), logic(3) }    
    
EnableState ::= TEXTUAL-CONVENTION
    STATUS       current
    DESCRIPTION
            "Represents the state of an enabling flag."
    SYNTAX       INTEGER { enabled(1), disabled(2) }

InputDataType ::= TEXTUAL-CONVENTION
    STATUS       current
    DESCRIPTION
            "Represents the type of data read at an input."
    SYNTAX       INTEGER { autodetect(1), temperature(2), humidity(3), analogue(4), contact(5), inactive(255) }


sinetica            	OBJECT IDENTIFIER ::= { enterprises 3711 }

v1       	OBJECT IDENTIFIER ::= { hawki2MIB 1 }	-- MIB variant number

objects  	OBJECT IDENTIFIER ::= { v1 1 }
traps    	OBJECT IDENTIFIER ::= { hawki2MIB 0 }

-- {{{ objects group

inputs      	OBJECT IDENTIFIER ::= { objects 1 }
outputs     	OBJECT IDENTIFIER ::= { objects 2 }

keypads     	OBJECT IDENTIFIER ::= { objects 4 }
acus        	OBJECT IDENTIFIER ::= { objects 5 }
access      	OBJECT IDENTIFIER ::= { objects 6 }
pdus        	OBJECT IDENTIFIER ::= { objects 7 }
 
inventory   	OBJECT IDENTIFIER ::= { objects 99 }
trapInfo    	OBJECT IDENTIFIER ::= { objects 100 }

-- }}} End of objects group

-- {{{ inputs group

-- The Hawk-i2 inputs can all be either temperature, humidity, analogue volts or contact state.
-- To deal with this there is one table to deal with all analogue-type inputs (temperature, humidity, analogue volts) and another for the contacts.
-- At any time an input is permitted to have an entry in one table only, depending on which type of input it is currently monitoring.

ipCommon	OBJECT IDENTIFIER ::= { inputs 1 }
ipTHA   	OBJECT IDENTIFIER ::= { inputs 2 }
ipContact	OBJECT IDENTIFIER ::= { inputs 3 }

-- {{{ ipCommon group

ipEnable	OBJECT IDENTIFIER ::= { ipCommon 1 }

-- {{{ ipEnable group

ipSelect  OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Selects the channel to be enabled or disabled by ipInsert. 
		A value of 0 selects no channel."
	DEFVAL { 0 }
	::= { ipEnable 1 }

ipInsert  OBJECT-TYPE
	SYNTAX      InputDataType
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Inserts or removes the channel selected by ipSelect - 
		causes an entry for that channel to be created or deleted in the relevant tables.
		- Read behaviour is undefined."
	::= { ipEnable 2 }

-- }}} End of ipEnable group

-- }}} End of ipCommon group
-- {{{ ipTHA - i.e. temperature, humidity and analogue Volts monitoring

ipTempScaleFlag   OBJECT-TYPE
	SYNTAX      INTEGER { celsius(1), fahrenheit(2), kelvin(3) }
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "Temperature scale (Celsius/Fahrenheit) for temperature monitoring."
	::= { ipTHA 1 }

ipTHATable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF	IpTHAEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A table giving data for all enabled inputs with analogue-type monitoring."
	::= { ipTHA 2 }

ipTHAEntry   OBJECT-TYPE
	SYNTAX      IpTHAEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing information about one analogue-type input."
	INDEX		{ ipTHAChan }
	::= { ipTHATable 1 }

IpTHAEntry ::= SEQUENCE {
	ipTHAChan   	INTEGER,
	ipTHARS     	RowStatus,
	ipTHAName   	DisplayString,
	ipTHALocn  	DisplayString,
	ipTHAAutoDetect	TruthValue,
	ipTHAType   	InputDataType,
	ipTHAValue  	INTEGER,
	ipTHAScaling	INTEGER,
	ipTHAOffset  	INTEGER,
	ipTHAHysteresis	INTEGER
		}

ipTHAChan    	OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The input number."
	::= { ipTHAEntry 1 }
							      
ipTHARS	OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The analogue-type input table row status."
	::= { ipTHAEntry 2 }

ipTHAName     	OBJECT-TYPE
	SYNTAX		DisplayString (SIZE(0..15))
	MAX-ACCESS	read-write
	STATUS		current
	DESCRIPTION
        "The name of this input"
	::= { ipTHAEntry 3 }

ipTHALocn     	OBJECT-TYPE
	SYNTAX		DisplayString (SIZE(0..4))
	MAX-ACCESS	read-only
	STATUS		current
	DESCRIPTION
		"A system-defined name for the physical location of this input, e.g. MCU."
	::= { ipTHAEntry 4 }

ipTHAAutoDetect 	OBJECT-TYPE
	SYNTAX      TruthValue
	MAX-ACCESS	read-write
	STATUS		current
	DESCRIPTION
        "Indicates that the type of data this input is monitoring is selected automatically."	
	::= { ipTHAEntry 5 }

ipTHAType	OBJECT-TYPE
	SYNTAX      InputDataType
	MAX-ACCESS	read-write
	STATUS		current
	DESCRIPTION
        "Indicates the type of data this input is monitoring."	
	::= { ipTHAEntry 6 }

ipTHAValue  OBJECT-TYPE
	SYNTAX      INTEGER (-200..1000)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
	    "The current reading in the relevant measurement units."
	::= { ipTHAEntry 7 }

ipTHAScaling  OBJECT-TYPE
    SYNTAX      INTEGER (0..100)
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Scaling factor for ipTHAValue when ipTHAType=analogue."
    ::= { ipTHAEntry 8 }

ipTHAOffset  OBJECT-TYPE
    SYNTAX      INTEGER (-100..100)
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Calibration offset in the same units as for ipTHAValue."	
    ::= { ipTHAEntry 9 }

ipTHAHysteresis  OBJECT-TYPE
    SYNTAX      INTEGER (-100..100)
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Hysteresis on threshold levels in the same units as for ipTHAValue."	
    ::= { ipTHAEntry 10 }

-- {{{ ipTHATrapsCfg group

ipTHATrapsCfg OBJECT IDENTIFIER ::= { ipTHA 3 }

-- {{{ ipTHAThreshTable

ipTHAThreshTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF	IpTHAThreshEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A table listing the trap threshold levels for all enabled inputs with analogue-type monitoring."
	::= { ipTHATrapsCfg 1 }

ipTHAThreshEntry   OBJECT-TYPE
	SYNTAX      IpTHAThreshEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing threshold information for one analogue-type input."
	INDEX		{ ipTHAThreshChan }
	::= { ipTHAThreshTable 1 }

IpTHAThreshEntry ::= SEQUENCE {
	ipTHAThreshChan 	INTEGER,
	ipTHAThreshRS   	RowStatus,
	ipTHAUCL        	INTEGER,
	ipTHAUWL        	INTEGER,
	ipTHALWL        	INTEGER,
	ipTHALCL        	INTEGER
		}

ipTHAThreshChan    	OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The input number."
	::= { ipTHAThreshEntry 1 }
							      
ipTHAThreshRS	OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The analogue-type input table row status."
	::= { ipTHAThreshEntry 2 }

ipTHAUCL  OBJECT-TYPE
	SYNTAX      INTEGER (-200..1000)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "The Upper Critical Limit for this input in the same units as for ipTHAValue."
	::= { ipTHAThreshEntry 3 }
 
ipTHAUWL  OBJECT-TYPE
    SYNTAX    INTEGER (-200..1000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "The Upper Warning Limit for this input in the same units as for ipTHAValue."
    ::= { ipTHAThreshEntry 4 }

ipTHALWL  OBJECT-TYPE
    SYNTAX    INTEGER (-200..1000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "The Lower Warning Limit for this input in the same units as for ipTHAValue."
    ::= { ipTHAThreshEntry 5 }
 
ipTHALCL  OBJECT-TYPE
    SYNTAX    INTEGER (-200..1000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "The Lower Critical Limit for this input in the same units as for ipTHAValue."
    ::= { ipTHAThreshEntry 6 }

-- }}} End of ipTHAThreshTable
-- {{{ ipTHATrapEnTable

ipTHATrapEnTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF	IpTHATrapEnEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "The table that controls trap enabling for all enabled inputs with analogue-type monitoring."
	::= { ipTHATrapsCfg 2 }

ipTHATrapEnEntry   OBJECT-TYPE
	SYNTAX      IpTHATrapEnEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing trap enabling information for one analogue-type input."
	INDEX		{ ipTHATrapEnChan }
	::= { ipTHATrapEnTable 1 }

IpTHATrapEnEntry ::= SEQUENCE {
	ipTHATrapEnChan 	INTEGER,
	ipTHATrapEnRS   	RowStatus,
	ipTHAUCLTrapEn  	TruthValue,
	ipTHAUWLTrapEn  	TruthValue,
	ipTHALWLTrapEn  	TruthValue,
	ipTHALCLTrapEn  	TruthValue
		}

ipTHATrapEnChan    	OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The input number."
	::= { ipTHATrapEnEntry 1 }
							      
ipTHATrapEnRS	OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The analogue-type input table row status."
	::= { ipTHATrapEnEntry 2 }

ipTHAUCLTrapEn  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Enables and disables input UCL alarm traps."
    ::= { ipTHATrapEnEntry 3 }

ipTHAUWLTrapEn  OBJECT-TYPE
	SYNTAX      TruthValue
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables and disables input UWL alarm traps."
	::= { ipTHATrapEnEntry 4 }

ipTHALWLTrapEn  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Enables and disables input LWL alarm traps."
    ::= { ipTHATrapEnEntry 5 }

ipTHALCLTrapEn  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Enables and disables input LCL alarm traps."
    ::= { ipTHATrapEnEntry 6 }

-- }}} End of ipTHATrapEnTable
-- {{{ ipTHATrapPerTable

ipTHATrapPerTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF	IpTHATrapPerEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "The table that controls trap repetition for all enabled inputs with analogue-type monitoring."
	::= { ipTHATrapsCfg 3 }

ipTHATrapPerEntry   OBJECT-TYPE
	SYNTAX      IpTHATrapPerEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing trap repetition information for one analogue-type input."
	INDEX		{ ipTHATrapPerChan }
	::= { ipTHATrapPerTable 1 }

IpTHATrapPerEntry ::= SEQUENCE {
	ipTHATrapPerChan 	INTEGER,
	ipTHATrapPerRS   	RowStatus,
	ipTHATrapUCLPer  	INTEGER,
	ipTHATrapUWLPer  	INTEGER,
	ipTHATrapLWLPer  	INTEGER,
	ipTHATrapLCLPer  	INTEGER
		}

ipTHATrapPerChan    	OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The input number."
	::= { ipTHATrapPerEntry 1 }
							      
ipTHATrapPerRS	OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The table row status."
	::= { ipTHATrapPerEntry 2 }

ipTHATrapUCLPer  OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
    ::= { ipTHATrapPerEntry 3 }

ipTHATrapUWLPer  OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
    ::= { ipTHATrapPerEntry 4 }

ipTHATrapLWLPer  OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
    ::= { ipTHATrapPerEntry 5 }

ipTHATrapLCLPer  OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
    ::= { ipTHATrapPerEntry 6 }

-- }}} End of ipTHATrapPerTable

-- }}} End of ipTHATrapsCfg group
-- {{{ ipTHA traps

-- To Be Added

-- }}} End of ipTHA traps

-- }}} End of ipTHA
-- {{{ ipContact 

ipContTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF	IpContEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A table listing the parameters and data for all enabled inputs with contact-type monitoring."
	::= { ipContact 1 }

ipContEntry   OBJECT-TYPE
	SYNTAX      IpContEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing information about one contact input."
	INDEX		{ ipContChan }
	::= { ipContTable 1 }

IpContEntry ::= SEQUENCE {
	ipContChan       	INTEGER,
	ipContRS          	RowStatus,
	ipContName        	DisplayString,
	ipContLocn      	DisplayString,
	ipContAutoDetect 	TruthValue,
	ipContNormState 	ContactState,
	ipContCurrState 	InputContactState,
	ipContTrigMode  	INTEGER,
	ipContReset       	Unsigned32,
	ipContTrapEn		INTEGER,
	ipContTrapPeriod  	INTEGER
			              }
							
ipContChan       OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The input number."
	::= { ipContEntry 1 }
							      
ipContRS       OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The contact input table row status."
	::= { ipContEntry 2 }

ipContName            OBJECT-TYPE
	SYNTAX		DisplayString (SIZE(0..15))
	MAX-ACCESS	read-write
	STATUS		current
	DESCRIPTION
        "The name of this input"	
	::= { ipContEntry 3 }

ipContLocn        OBJECT-TYPE
	SYNTAX		DisplayString (SIZE(0..4))
	MAX-ACCESS	read-only
	STATUS		current
	DESCRIPTION
		"A system-defined name for the physical location of this input, e.g. MCU."
	::= { ipContEntry 4 }

ipContAutoDetect      OBJECT-TYPE
    SYNTAX      TruthValue
	MAX-ACCESS	read-write
	STATUS		current
	DESCRIPTION
        "Indicates that the type of data this input is monitoring is selected automatically."	
	::= { ipContEntry 5 }

ipContNormState     OBJECT-TYPE
	SYNTAX      ContactState
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"The normal state for this contact."
	::= { ipContEntry 6 }

ipContCurrState    OBJECT-TYPE
	SYNTAX      InputContactState
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The current state of this contact."
	::= { ipContEntry 7 }

ipContTrigMode     OBJECT-TYPE
	SYNTAX      INTEGER { positiveEdge(1), negativeEdge(2), level(3) }
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"The contact trigger mode, level, +ve edge, -ve edge."
	::= { ipContEntry 8 }

ipContReset           OBJECT-TYPE
	SYNTAX      Unsigned32
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Resets the contact after triggering in edge mode."
	::= { ipContEntry 9 }

ipContTrapEn  OBJECT-TYPE
    SYNTAX      INTEGER { critical(1), warning(2), information(3), disabled(255) }
	MAX-ACCESS    read-write
	STATUS    current
	DESCRIPTION
        "Configure contact input traps."
	::= { ipContEntry 10 }

ipContTrapPeriod  OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
    ::= { ipContEntry 11 }

-- {{{ ipContact traps
                          	          	
-- To Be Added

-- }}} End of ipContact traps

-- }}} End of ipContact

-- }}} End of ip group
-- {{{ outputs group

opEnable	OBJECT IDENTIFIER ::= { outputs 1 }

-- {{{ opEnable group

opSelect  OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Selects the channel to be enabled or disabled by opEnable. 
		A value of 0 selects no channel."
	DEFVAL { 0 }
	::= { opEnable 1 }

opInsert  OBJECT-TYPE
	SYNTAX      EnableState
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables or disables the channel selected by opSelect - 
		causes an entry for that channel to be created or deleted in the relevant tables.
		- Read behaviour is undefined."
	::= { opEnable 2 }

-- }}} End of opEnable group
-- {{{ opTable

opTable    OBJECT-TYPE
	SYNTAX      SEQUENCE OF	OpEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A table listing the parameters and data for all outputs that are enabled and available (i.e. its extension unit is connected)."
	::= { outputs 2 }

opEntry    OBJECT-TYPE
	SYNTAX      OpEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION	
		"A conceptual row containing information about one output."
	INDEX { opChan }
	::= { opTable 1 }

OpEntry ::= SEQUENCE {
	opChan      	INTEGER,
	opRS        	RowStatus,
	opName      	DisplayString,
	opLocn      	DisplayString,
	opNormState 	RelayState,
	opCurrState  	RelayState,
	opOnDelTime   	Unsigned32,
	opOffDelTime  	Unsigned32,
	opBooleanEqn    DisplayString,
	opTrapEn    	INTEGER,
	opTrapPeriod	INTEGER,
	opControlState	OutputControlState
		}

opChan        	OBJECT-TYPE
	SYNTAX      INTEGER  (0..18)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The output number."
	::= { opEntry 1 }

opRS    	OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The contact input table row status."
	::= { opEntry 2 }

opName         	OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"A user-defined name for this output."
	::= { opEntry 3 }

opLocn         	OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..4))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"A system-defined name for the physical location of this output, e.g. MCU."
	::= { opEntry 4 }

opNormState  	OBJECT-TYPE
	SYNTAX      RelayState
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Sets or reads the required normal state of this output."
	::= { opEntry 5 }
          		
opCurrState 	OBJECT-TYPE
	SYNTAX      RelayState
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Reads the current state of this output."
	::= { opEntry 6 }   
	
opOnDelTime  	OBJECT-TYPE
	SYNTAX      Unsigned32 
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION	
		"Sets the 'on' delay time for this output."
	::= { opEntry 7 }

opOffDelTime 	OBJECT-TYPE
	SYNTAX      Unsigned32 
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION	
		"Sets the 'off' delay time for this output."
	::= { opEntry 8 }

opBooleanEqn     	OBJECT-TYPE
    SYNTAX 	    DisplayString
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Boolean equation string"	
    ::= { opEntry 9 } 
    
opTrapEn  	OBJECT-TYPE
    SYNTAX      INTEGER { critical(1), warning(2), information(3), disabled(255) }
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Configure output traps."
    ::= { opEntry 10 }

opTrapPeriod	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
    ::= { opEntry 11 }  
    
opControlState	OBJECT-TYPE
    SYNTAX    	OutputControlState
    MAX-ACCESS  read-write
    STATUS    	current
    DESCRIPTION
        "Reads the current control state of an output."
    ::= { opEntry 12 }  

-- }}} End of opTable
-- {{{ outputs traps

-- To Be Added

-- }}} End of outputs traps

-- }}} End of outputs group
-- {{{ keypads group
                     
kpEnable      	OBJECT IDENTIFIER ::= { keypads 1 }

-- {{{ kpEnable group

kpSelect  OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Selects the keypad to be enabled or disabled by kpEnable. 
		A value of 0 selects no keypad."
	DEFVAL { 0 }
	::= { kpEnable 1 }

kpInsert  OBJECT-TYPE
	SYNTAX      EnableState
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables or disables the keypad selected by kpSelect - 
		causes an entry for that keypad to be created or deleted in the relevant tables.
		- Read behaviour is undefined."
	::= { kpEnable 2 }

-- }}} End of kpEnable group
-- {{{ kpTable

kpCtlTable    OBJECT-TYPE
	SYNTAX      SEQUENCE OF	KpCtlEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A table listing the parameters and data for the keypads."
	::= { keypads 2 }

kpCtlEntry    OBJECT-TYPE
	SYNTAX      KpCtlEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION	
		"A conceptual row containing information about one keypad."
	INDEX { kpNumber }
	::= { kpCtlTable 1 }

KpCtlEntry ::= SEQUENCE {
	kpNumber        		INTEGER,
	kpRS            		RowStatus,
	kpManufacturer     		DisplayString,
	kpName             		DisplayString,
	kpDoorLatchTimeOut      Unsigned32,
	kpRtnToStndbyTimeOut	INTEGER,
	kpEntryCodeValid   		TruthValue,
	kpDoorOpenTimeOut   	INTEGER,
	kpRemoteDoorOpen   		TruthValue,
	kpInUseTrapEn      		INTEGER
		}

kpNumber        OBJECT-TYPE
	SYNTAX      INTEGER  (1..2)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The keypad number."
	::= { kpCtlEntry 1 }

kpRS	OBJECT-TYPE
	SYNTAX      RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The keypad table row status."
	::= { kpCtlEntry 2 }

kpManufacturer  OBJECT-TYPE
    SYNTAX DisplayString (SIZE(0..15))
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "The name of the manufacturer of the keypad."
    ::= { kpCtlEntry 3 }

kpName  OBJECT-TYPE
    SYNTAX DisplayString (SIZE(0..15))
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "A name identifying the keypad."
    ::= { kpCtlEntry 4 }

kpDoorLatchTimeOut		OBJECT-TYPE
	SYNTAX      Unsigned32
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "Time-out value in seconds for which the door latch is held open."
	::= { kpCtlEntry 5 }

kpRtnToStndbyTimeOut	OBJECT-TYPE
    SYNTAX      INTEGER (0..99)
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Time-out value in seconds for Return to Standby Mode"
    ::= { kpCtlEntry 6 }

kpEntryCodeValid  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Set if previous keypad entry was valid."
    ::= { kpCtlEntry 7 }  
    
kpDoorOpenTimeOut  OBJECT-TYPE
	SYNTAX      INTEGER (0..99)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Time-out value in seconds for Door Open."
	::= { kpCtlEntry 8 }

kpRemoteDoorOpen  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Set to open the door."
    ::= { kpCtlEntry 9 }
    
kpInUseTrapEn  OBJECT-TYPE
    SYNTAX      INTEGER { critical(1), warning(2), information(3), disabled(255) }
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "'keypad in use' trap enable"
    ::= { kpCtlEntry 10 }
    
-- }}} End of kpTable
-- {{{ keypads traps

-- To Be Added

-- }}} End of keypads traps

-- }}} End of keypads group
-- {{{ acus group
                     
acuEnable      	OBJECT IDENTIFIER ::= { acus 1 }

-- {{{ acuEnable group

acuSelect  OBJECT-TYPE
	SYNTAX      INTEGER  (0..24)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Selects the ACU to be enabled or disabled by acuEnable. 
		A value of 0 selects no ACU."
	DEFVAL { 0 }
	::= { acuEnable 1 }

acuInsert  OBJECT-TYPE
	SYNTAX      EnableState
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables or disables the ACU selected by acuSelect - 
		causes an entry for that ACU to be created or deleted in the relevant tables.
		- Read behaviour is undefined."
	::= { acuEnable 2 }

-- }}} End of acuEnable group
-- {{{ acuTable

acuCtlTable    OBJECT-TYPE
	SYNTAX      SEQUENCE OF	AcuCtlEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A table listing the parameters and data for the ACUs."
	::= { acus 2 }

acuCtlEntry    OBJECT-TYPE
	SYNTAX      AcuCtlEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION	
		"A conceptual row containing information about one ACU."
	INDEX { acuNumber }
	::= { acuCtlTable 1 }

AcuCtlEntry ::= SEQUENCE {
	acuNumber           	INTEGER,
	acuCtlRS            	RowStatus,
	acuManufacturer     	DisplayString,
	acuName             	DisplayString,
	acuDoorLatchTimeOut     Unsigned32,
	acuRtnToStndbyTimeOut	INTEGER,
	acuEntryCodeValid   	TruthValue,
	acuDoorOpenTimeOut   	INTEGER,
	acuRemoteDoorOpen   	TruthValue,
	acuInUseTrapEn      	INTEGER
		}

acuNumber        OBJECT-TYPE
	SYNTAX      INTEGER  (1..6)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The ACU number."
	::= { acuCtlEntry 1 }

acuCtlRS	OBJECT-TYPE
	SYNTAX      RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The ACU table row status."
	::= { acuCtlEntry 2 }

acuManufacturer  OBJECT-TYPE
    SYNTAX DisplayString (SIZE(0..15))
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "The name of the manufacturer of the ACU."
    ::= { acuCtlEntry 3 }

acuName  OBJECT-TYPE
    SYNTAX DisplayString (SIZE(0..15))
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "A name identifying the ACU."
    ::= { acuCtlEntry 4 }

acuDoorLatchTimeOut		OBJECT-TYPE
	SYNTAX      Unsigned32
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "Time-out value in seconds for which the door latch is held open."
	::= { acuCtlEntry 5 }

acuRtnToStndbyTimeOut	OBJECT-TYPE
    SYNTAX      INTEGER (0..99)
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Time-out value in seconds for Return to Standby Mode"
    ::= { acuCtlEntry 6 }

acuEntryCodeValid  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Set if previous ACU entry was valid."
    ::= { acuCtlEntry 7 }  
    
acuDoorOpenTimeOut  OBJECT-TYPE
	SYNTAX      INTEGER (0..99)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Time-out value in seconds for Door Open."
	::= { acuCtlEntry 8 }

acuRemoteDoorOpen  OBJECT-TYPE
    SYNTAX      TruthValue
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "Set to open the door."
    ::= { acuCtlEntry 9 }
    
acuInUseTrapEn  OBJECT-TYPE
    SYNTAX      INTEGER { critical(1), warning(2), information(3), disabled(255) }
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "'ACU in use' trap enable"
    ::= { acuCtlEntry 10 }
    
-- }}} End of acuTable
-- {{{ acus traps

-- To Be Added

-- }}} End of acus traps

-- }}} End of acus group
-- {{{ access group

accUserCtl      	OBJECT IDENTIFIER ::= { access 1 }

-- {{{ accUserCtl group

accUserInstance  OBJECT-TYPE
	SYNTAX      Unsigned32
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"A value of 0 causes an access user to be created in the relevant tables.
		A non-zero value causes the nominated access user table entries to be deleted."
	::= { accUserCtl 1 }

-- {{{ accUserTable

accUserTable    OBJECT-TYPE
	SYNTAX      SEQUENCE OF	AccUserEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A table controlling the access users."
	::= { accUserCtl 2 }

accUserEntry    OBJECT-TYPE
	SYNTAX      AccUserEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
	    "A conceptual row containing information about one ACU user."
	INDEX       { accUserNumber }
	::= { accUserTable 1 }

AccUserEntry ::= SEQUENCE {
	accUserNumber    	INTEGER,
	accUserRS        	RowStatus,
	accUserName      	DisplayString,
	accUserCode      	OCTET STRING,
	accUserPrivileges	DisplayString,
	accUserExpires		DisplayString
		}

accUserNumber   OBJECT-TYPE
	SYNTAX      INTEGER  (0..20)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The the access user-table entry number."
	::= { accUserEntry 1 }

accUserRS       OBJECT-TYPE
	SYNTAX      RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The access user table row status."
	::= { accUserEntry 2 }

accUserName    OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"A name identifying the access user."
	::= { accUserEntry 3 }

accUserCode    OBJECT-TYPE
	SYNTAX      OCTET STRING (SIZE (0..15))
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "The user's access code."
	::= { accUserEntry 4 }

accUserPrivileges    OBJECT-TYPE
	SYNTAX      DisplayString (SIZE (0..11))
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "The ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings."
	::= { accUserEntry 5 }

accUserExpires    OBJECT-TYPE
	SYNTAX      DisplayString
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
	    "A text string which specifies when the access code in the row expires. The format is defined by the application."
	::= { accUserEntry 6 }

-- }}} End of accUserTable

accUserSetup  OBJECT-TYPE
	SYNTAX      OCTET STRING
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"A free form octet string for programming accUserTable. The format is defined by the application."
	::= { accUserCtl 3 }

-- }}} End of accUserCtl group
-- {{{ pdus group

pduCommon 	OBJECT IDENTIFIER ::= { pdus 1 }
pduOutlets	OBJECT IDENTIFIER ::= { pdus 2 }
pduMonitor	OBJECT IDENTIFIER ::= { pdus 3 }

-- {{{ pduCommon group

pdusEnable	OBJECT IDENTIFIER ::= { pduCommon 1 }

-- {{{ pduEnable group

pduSelect  OBJECT-TYPE
	SYNTAX      INTEGER  (0..6)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Selects the PDU to be enabled or disabled by pduEnable. 
		A value of 0 selects no PDU."
	DEFVAL { 0 }
	::= { pdusEnable 1 }

pduInsert  OBJECT-TYPE
	SYNTAX      EnableState
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables or disables the PDU selected by pduSelect - 
		causes an entry for that PDU to be created or deleted in the relevant tables.
		- Read behaviour is undefined."
	::= { pdusEnable 2 }

-- }}} End of pduEnable group
-- {{{ pduTable

pduTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF PduEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A table containing information about each enabled PDU."
	::= { pduCommon 2 }

pduEntry   OBJECT-TYPE
	SYNTAX      PduEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing information about one PDU."
	INDEX { pduNumber }
	::= { pduTable 1 }

PduEntry ::= SEQUENCE {
	pduNumber    	INTEGER,
	pduRS       	RowStatus,
	pduName        	DisplayString,
	pduOutEn    	TruthValue,
	pduMonEn    	TruthValue,
	pduCommsFail   	INTEGER
		}

pduNumber      OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number."
	::= { pduEntry 1 }

pduRS   OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduEntry 2 }

pduName OBJECT-TYPE
	SYNTAX  	DisplayString(SIZE(0..15))
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"A string identifying the PDU."
	::= { pduEntry 3}

pduOutEn OBJECT-TYPE
	SYNTAX      TruthValue
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table."
	::= {pduEntry 4 }

pduMonEn OBJECT-TYPE
	SYNTAX      TruthValue
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"Enables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table."
	::= {pduEntry 5 }

pduCommsFail OBJECT-TYPE
	SYNTAX  	INTEGER { commsGood(1), commsFailed(2), commsBadData(3)}
	MAX-ACCESS	read-only
	STATUS  	current
	DESCRIPTION
		"Indicates comms. status for the PDU."
	::= {pduEntry 6 }

-- }}} End of pduTable

-- }}} End of pduCommon group
-- {{{ pduOutlets group

pduOutAll	OBJECT IDENTIFIER ::= { pduOutlets 1 }

-- {{{ pduOutAll group

pduOutCycleAll OBJECT-TYPE
	SYNTAX  	INTEGER { up(1), down(2) }
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Sets the required state of all power outlets on all connected PDUs."
	::= { pduOutAll 1 }	   

pduOutCycleAllPwd OBJECT-TYPE
	SYNTAX  	DisplayString(SIZE(0..7))
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Controls access to setting the required state of all power outlets on all connected PDUs."
	::= { pduOutAll 2 }

pduOutCycleAllAbort OBJECT-TYPE
	SYNTAX  	Unsigned32
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Abort command for pduOutCycleAll."
	::= { pduOutAll 3 }	   

pduOutGlobalCycleDelay OBJECT-TYPE
	SYNTAX  	Unsigned32
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Sets the delay period for pduOutCycleAll and pduOutCycle commands before they start to execute."
	::= { pduOutAll 4 }
	
pduOutGlobalRebootTime OBJECT-TYPE
	SYNTAX  	Unsigned32
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Sets the off to on delay period for a pdu outlet reboot."
	::= { pduOutAll 5 }	
	
pduOutGlobalCycleAbortTime OBJECT-TYPE
	SYNTAX  	Unsigned32
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Time delay to abort power outlet setting task."
	::= { pduOutAll 6 }	 		   

-- }}} End of pduOutAll group
-- {{{ pduOutTable

pduOutCmnTable   OBJECT-TYPE
	SYNTAX  	SEQUENCE OF PduOutCmnEntry
	MAX-ACCESS	not-accessible
	STATUS  	current
	DESCRIPTION
		"A table containing information about the power outlets of all PDUs enabled for outlet control."
	::= { pduOutlets 2 }

pduOutCmnEntry   OBJECT-TYPE
	SYNTAX  	PduOutCmnEntry
	MAX-ACCESS	not-accessible
	STATUS  	current
	DESCRIPTION
		"A conceptual row containing information about the power outlets of one PDU."
	INDEX { pduOutCmnPduNumber }
	::= { pduOutCmnTable 1 }

PduOutCmnEntry ::= SEQUENCE {
	pduOutCmnPduNumber 		INTEGER,
	pduOutCmnRS        		RowStatus,
	pduNumOfOutlets      	INTEGER,
	pduOutCycle         	INTEGER,
	pduOutCyclePwd      	DisplayString,
	pduOutCycleAbortTask	Unsigned32,
	pduOutCycleAbortTime	Unsigned32
		}

pduOutCmnPduNumber      OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number."
	::= { pduOutCmnEntry 1 }

pduOutCmnRS   OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduOutCmnEntry 2 }

pduNumOfOutlets OBJECT-TYPE
	SYNTAX      INTEGER (1..32)
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"The number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU."
	::= { pduOutCmnEntry 3 }	   

pduOutCycle OBJECT-TYPE
	SYNTAX  	INTEGER { up(1), down(2) }
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Sets the required state of all power outlets on the PDU."
	::= { pduOutCmnEntry 4 }	   

pduOutCyclePwd OBJECT-TYPE
	SYNTAX  	DisplayString(SIZE(0..7))
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"Password controling access to setting the required state of all power outlets on the PDU."
	::= { pduOutCmnEntry 5 }	   

pduOutCycleAbortTask  OBJECT-TYPE
    SYNTAX  	Unsigned32 
    MAX-ACCESS	read-write
    STATUS  	current
    DESCRIPTION
        "Abort power outlet setting task."
    ::= { pduOutCmnEntry 6 }

pduOutCycleAbortTime  OBJECT-TYPE
    SYNTAX    Unsigned32 
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
		"Time delay to abort power outlet setting task."
    ::= { pduOutCmnEntry 7 }

-- }}} End of pduOutCmnTable
-- {{{ pduOutTable

pduOutTable	OBJECT-TYPE
	SYNTAX		SEQUENCE OF	PduOutEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A table listing the states and descriptions for each outlet on the PDU."
	::= { pduOutlets 3 }

pduOutEntry 	OBJECT-TYPE
	SYNTAX      PduOutEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A row containing information about one PDU outlet."
	INDEX { pduOutPduNumber, pduOutNumber }
	::= { pduOutTable 1 }

PduOutEntry ::= SEQUENCE {
	pduOutPduNumber 	INTEGER,
	pduOutNumber     	INTEGER,
	pduOutRS        	RowStatus,
	pduOutName      	DisplayString,
	pduOutOn        	INTEGER,
	pduOutPwd  			DisplayString,
	pduOutCycleDelay	Unsigned32,
	pduOutRebootPeriod	Unsigned32
		}

pduOutPduNumber     	OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number on which the outlet resides."
	::= { pduOutEntry 1 }

pduOutNumber     	OBJECT-TYPE
	SYNTAX      INTEGER  (1..32)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The outlet number."
	::= { pduOutEntry 2 }

pduOutRS 	OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduOutEntry 3 }

pduOutName      	OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..31))
	MAX-ACCESS  read-write
	STATUS      current
	DESCRIPTION
		"A name identifying the outlet."
	::= { pduOutEntry 4 }

pduOutOn        	OBJECT-TYPE
    SYNTAX      INTEGER { on(1), off(2), reboot(3)}
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"The current state for this outlet."
	::= { pduOutEntry 5 }

pduOutPwd  	OBJECT-TYPE
	SYNTAX  	DisplayString (SIZE(0..7))
	MAX-ACCESS	read-write
	STATUS  	current
	DESCRIPTION
		"The password for this outlet."
	::= { pduOutEntry 6 }

pduOutCycleDelay	OBJECT-TYPE
	SYNTAX  	Unsigned32 
	MAX-ACCESS	read-only
	STATUS  	current
	DESCRIPTION
		"The on/off delay for this outlet in seconds."
	::= { pduOutEntry 7 }

pduOutRebootPeriod	OBJECT-TYPE
	SYNTAX  	Unsigned32 
	MAX-ACCESS	read-only
	STATUS  	current
	DESCRIPTION
		"The pduOutOn reboot off period for this outlet in seconds."
	::= { pduOutEntry 8 }

-- }}} End of pduOutTable

-- }}} End of pduOut group
-- {{{ pduMonitor group

-- {{{ pduMonTable

pduMonTable    	OBJECT-TYPE
	SYNTAX      SEQUENCE OF PduMonEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A table containing monitor information for all PDUs enabled for monitoring."
	::= { pduMonitor 1 }

pduMonEntry   OBJECT-TYPE
	SYNTAX      PduMonEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing monitor information for one PDU."
	INDEX { pduMonPduNumber }
	::= { pduMonTable 1 }

PduMonEntry ::= SEQUENCE {
	pduMonPduNumber			INTEGER,
	pduMonRS    			RowStatus,
	pduRMSVoltsValue	   	INTEGER,
	pduRMSAmpsValue    		INTEGER,
	pduTotalEnergyValue		INTEGER,
	pduMeanKVAValue			INTEGER,
	pduMeanKWattsValue		INTEGER,
	pduPwrFactorValue		INTEGER
		}

pduMonPduNumber      OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number."
	::= { pduMonEntry 1 }

pduMonRS   OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduMonEntry 2 }

pduRMSVoltsValue  OBJECT-TYPE
    SYNTAX  	INTEGER (0..500)
    MAX-ACCESS	read-only
    STATUS	    current
    DESCRIPTION
		"RMS Volts value in volts"
    ::= { pduMonEntry 3 }
    
pduRMSAmpsValue  OBJECT-TYPE
    SYNTAX  	INTEGER (0..500)
    MAX-ACCESS	read-only
    STATUS  	current
    DESCRIPTION
		"RMS current value in 0.1 Amps"
    ::= { pduMonEntry 4 }
    
pduTotalEnergyValue  OBJECT-TYPE
    SYNTAX    INTEGER (0..9999999)
    MAX-ACCESS    read-only
    STATUS    current
    DESCRIPTION
		"Total energy value in 0.1 kWh"
    ::= { pduMonEntry 5 }

pduMeanKVAValue  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-only
    STATUS    current
    DESCRIPTION
		"Kilo Volt-Amperes value in 0.1 kVA"
    ::= { pduMonEntry 6 }

pduMeanKWattsValue  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-only
    STATUS    current
    DESCRIPTION
		"Kilo Watts value in 0.1 kW"
    ::= { pduMonEntry 7 }

pduPwrFactorValue  OBJECT-TYPE
    SYNTAX    INTEGER (0..100)
    MAX-ACCESS    read-only
    STATUS    current
    DESCRIPTION
		"Power factor value in 0.01"
    ::= { pduMonEntry 8 }

-- }}} End of pduMonTable
-- {{{ pduTrapThreshTable

pduTrapThreshTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF PduTrapThreshEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A table containing information about the trap threshold values for all PDUs enabled for monitoring."
	::= { pduMonitor 2 }

pduTrapThreshEntry   OBJECT-TYPE
	SYNTAX      PduTrapThreshEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing information about the trap threshold values for one PDU."
	INDEX { pduTrapThreshPduNumber }
	::= { pduTrapThreshTable 1 }

PduTrapThreshEntry ::= SEQUENCE {
	pduTrapThreshPduNumber 	INTEGER,
	pduTrapThreshRS     	RowStatus,
	pduRMSVoltsUCL	    	INTEGER,
	pduRMSVoltsUWL      	INTEGER,
	pduRMSVoltsLWL      	INTEGER,
	pduRMSVoltsLCL	    	INTEGER,
	pduRMSAmpsUCL       	INTEGER,
	pduRMSAmpsUWL       	INTEGER,
	pduRMSAmpsLWL       	INTEGER,
	pduRMSAmpsLCL       	INTEGER,
	pduEnergyUCL        	INTEGER,
	pduEnergyUWL        	INTEGER,
	pduMeanKVAUCL			INTEGER,
	pduMeanKVAUWL			INTEGER,
	pduMeanKVALWL			INTEGER,
	pduMeanKVALCL			INTEGER,
	pduMeanKWattsUCL		INTEGER,
	pduMeanKWattsUWL		INTEGER,
	pduMeanKWattsLWL		INTEGER,
	pduMeanKWattsLCL		INTEGER,
	pduPwrFactorUCL			INTEGER,
	pduPwrFactorUWL			INTEGER,
	pduPwrFactorLWL			INTEGER,
	pduPwrFactorLCL			INTEGER
		}

pduTrapThreshPduNumber      OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number."
	::= { pduTrapThreshEntry 1 }

pduTrapThreshRS   OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduTrapThreshEntry 2 }

pduRMSVoltsUCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms UCL value in volts"
    ::= { pduTrapThreshEntry 3 }

pduRMSVoltsUWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms UWL value in volts"
    ::= { pduTrapThreshEntry 4 }

pduRMSVoltsLWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms LWL value in volts"
    ::= { pduTrapThreshEntry 5 }

pduRMSVoltsLCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms LCL value in volts"
    ::= { pduTrapThreshEntry 6 }

pduRMSAmpsUCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms UCL value in 0.1 amps"
    ::= { pduTrapThreshEntry 7 }

pduRMSAmpsUWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms UWL value in 0.1 amps"
    ::= { pduTrapThreshEntry 8 }

pduRMSAmpsLWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms LWL value in 0.1 amps"
    ::= { pduTrapThreshEntry 9 }

pduRMSAmpsLCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..500)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "rms LCL value in 0.1 amps"
    ::= { pduTrapThreshEntry 10 }

pduEnergyUCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..9999999)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Total energy UCL value in 0.1 kWh"
    ::= { pduTrapThreshEntry 11 }

pduEnergyUWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..9999999)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Total energy UWL value in 0.1 kWh"
    ::= { pduTrapThreshEntry 12 }

pduMeanKVAUCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean kVA UCL value in 0.1 kVA"
    ::= { pduTrapThreshEntry 13 }

pduMeanKVAUWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean kVA UWL value in 0.1 kVA"
    ::= { pduTrapThreshEntry 14 }

pduMeanKVALWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean kVA LWL value in 0.1 kVA"
    ::= { pduTrapThreshEntry 15 }

pduMeanKVALCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean kVA LCL value in 0.1 kVA"
    ::= { pduTrapThreshEntry 16 }

pduMeanKWattsUCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean power UCL value in 0.1 kW"
    ::= { pduTrapThreshEntry 17 }

pduMeanKWattsUWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean power UWL value in 0.1 kW"
    ::= { pduTrapThreshEntry 18 }

pduMeanKWattsLWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean power LWL value in 0.1 kW"
    ::= { pduTrapThreshEntry 19 }

pduMeanKWattsLCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Mean power LCL value in 0.1 kW"
    ::= { pduTrapThreshEntry 20 }

pduPwrFactorUCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Power factor UCL value in 0.01"
    ::= { pduTrapThreshEntry 21 }

pduPwrFactorUWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Power factor UWL value in 0.01"
    ::= { pduTrapThreshEntry 22 }

pduPwrFactorLWL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Power factor LWL value in 0.01"
    ::= { pduTrapThreshEntry 23 }

pduPwrFactorLCL  OBJECT-TYPE
    SYNTAX    INTEGER (0..100)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Power factor LCL value in 0.01"
    ::= { pduTrapThreshEntry 24 }

-- }}} End of pduTrapThreshTable
-- {{{ pduTrapEnTable

pduTrapEnTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF PduTrapEnEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"The table which controls threshold value trap enabling for all PDUs enabled for monitoring."
	::= { pduMonitor 3 }

pduTrapEnEntry   OBJECT-TYPE
	SYNTAX      PduTrapEnEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing information about one PDU."
	INDEX { pduTrapEnPduNumber }
	::= { pduTrapEnTable 1 }

PduTrapEnEntry ::= SEQUENCE {
	pduTrapEnPduNumber     		INTEGER,
	pduTrapEnRS         		RowStatus,
	pduRMSVoltsUCLTrapEn   		TruthValue,
	pduRMSVoltsUWLTrapEn   		TruthValue,
	pduRMSVoltsLWLTrapEn   		TruthValue,
	pduRMSVoltsLCLTrapEn   		TruthValue,
	pduRMSAmpsUCLTrapEn    		TruthValue,
	pduRMSAmpsUWLTrapEn    		TruthValue,
	pduRMSAmpsLWLTrapEn    		TruthValue,
	pduRMSAmpsLCLTrapEn    		TruthValue,
	pduEnergyUCLTrapEn  		TruthValue,
	pduEnergyUWLTrapEn  		TruthValue,
	pduMeanKVAUCLTrapEn    		TruthValue,
	pduMeanKVAUWLTrapEn    		TruthValue,
	pduMeanKVALWLTrapEn    		TruthValue,
	pduMeanKVALCLTrapEn    		TruthValue,
	pduMeanKWattsUCLTrapEn   	TruthValue,
	pduMeanKWattsUWLTrapEn   	TruthValue,
	pduMeanKWattsLWLTrapEn   	TruthValue,
	pduMeanKWattsLCLTrapEn		TruthValue,
	pduPwrFactorUCLTrapEn    	TruthValue,
	pduPwrFactorUWLTrapEn    	TruthValue,
	pduPwrFactorLWLTrapEn    	TruthValue,
	pduPwrFactorLCLTrapEn    	TruthValue
		}

pduTrapEnPduNumber      OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number."
	::= { pduTrapEnEntry 1 }

pduTrapEnRS   OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduTrapEnEntry 2 }

pduRMSVoltsUCLTrapEn  OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS	read-write
    STATUS  	current
    DESCRIPTION
        "Enables Volts UCL trap."
    ::= { pduTrapEnEntry 3 }

pduRMSVoltsUWLTrapEn  OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables UWL Volts trap."
    ::= { pduTrapEnEntry 4 }

pduRMSVoltsLWLTrapEn  OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables LWL Volts trap."
    ::= { pduTrapEnEntry 5 }

pduRMSVoltsLCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables LCL Volts trap."
    ::= { pduTrapEnEntry 6 }

pduRMSAmpsUCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables UCL current trap."
    ::= { pduTrapEnEntry 7 }

pduRMSAmpsUWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables UWL current trap."
    ::= { pduTrapEnEntry 8 }

pduRMSAmpsLWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables LWL current trap."
    ::= { pduTrapEnEntry 9 }

pduRMSAmpsLCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables LCL current trap."
    ::= { pduTrapEnEntry 10 }

pduEnergyUCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables UCL total energy trap."
    ::= { pduTrapEnEntry 11 }

pduEnergyUWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
	MAX-ACCESS    read-write
	STATUS    current
	DESCRIPTION
		"Enables UWL total energy trap."
	::= { pduTrapEnEntry 12 }

pduMeanKVAUCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean kVA UCL trap."
    ::= { pduTrapEnEntry 13 }

pduMeanKVAUWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean kVA UWL trap."
    ::= { pduTrapEnEntry 14 }

pduMeanKVALWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean kVA LWL trap."
    ::= { pduTrapEnEntry 15 }

pduMeanKVALCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean kVA LCL trap."
    ::= { pduTrapEnEntry 16 }

pduMeanKWattsUCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean power UCL trap."
    ::= { pduTrapEnEntry 17 }

pduMeanKWattsUWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean power UWL trap."
    ::= { pduTrapEnEntry 18 }

pduMeanKWattsLWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean power LWL trap."
    ::= { pduTrapEnEntry 19 }

pduMeanKWattsLCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables mean power LCL trap."
    ::= { pduTrapEnEntry 20 }

pduPwrFactorUCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables power factor UCL trap."
    ::= { pduTrapEnEntry 21 }

pduPwrFactorUWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables power factor UWL trap."
    ::= { pduTrapEnEntry 22 }

pduPwrFactorLWLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables power factor LWL trap."
    ::= { pduTrapEnEntry 23 }

pduPwrFactorLCLTrapEn	OBJECT-TYPE
	SYNTAX  	TruthValue
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Enables power factor LCL trap."
    ::= { pduTrapEnEntry 24 }

-- }}} End of pduTrapEnTable
-- {{{ pduTrapPerTable

pduTrapPerTable   OBJECT-TYPE
	SYNTAX      SEQUENCE OF PduTrapPerEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"The table which controls threshold value trap repetition for all PDUs enabled for monitoring."
	::= { pduMonitor 4 }

pduTrapPerEntry   OBJECT-TYPE
	SYNTAX      PduTrapPerEntry
	MAX-ACCESS  not-accessible
	STATUS      current
	DESCRIPTION
		"A conceptual row containing information about one PDU."
	INDEX { pduTrapPduNumber }
	::= { pduTrapPerTable 1 }

PduTrapPerEntry ::= SEQUENCE {
	pduTrapPduNumber        INTEGER,
	pduTrapPerRS         	RowStatus,
	pduRMSVoltsUCLTrapPer  	INTEGER,
	pduRMSVoltsUWLTrapPer  	INTEGER,
	pduRMSVoltsLWLTrapPer  	INTEGER,
	pduRMSVoltsLCLTrapPer  	INTEGER,
	pduRMSAmpsUCLTrapPer   	INTEGER,
	pduRMSAmpsUWLTrapPer   	INTEGER,
	pduRMSAmpsLWLTrapPer   	INTEGER,
	pduRMSAmpsLCLTrapPer   	INTEGER,
	pduEnergyUCLTrapPer  	INTEGER,
	pduEnergyUWLTrapPer  	INTEGER,
	pduMeanKVAUCLTrapPer   	INTEGER,
	pduMeanKVAUWLTrapPer   	INTEGER,
	pduMeanKVALWLTrapPer   	INTEGER,
	pduMeanKVALCLTrapPer   	INTEGER,
	pduMeanKWattsUCLTrapPer	INTEGER,
	pduMeanKWattsUWLTrapPer INTEGER,
	pduMeanKWattsLWLTrapPer INTEGER,
	pduMeanKWattsLCLTrapPer INTEGER,
	pduPwrFactorUCLTrapPer  INTEGER,
	pduPwrFactorUWLTrapPer  INTEGER,
	pduPwrFactorLWLTrapPer  INTEGER,
	pduPwrFactorLCLTrapPer  INTEGER
		}

pduTrapPduNumber      OBJECT-TYPE
	SYNTAX      INTEGER  (1..8)
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU number."
	::= { pduTrapPerEntry 1 }

pduTrapPerRS   OBJECT-TYPE
	SYNTAX		RowStatus
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The PDU table row status."
	::= { pduTrapPerEntry 2 }

pduRMSVoltsUCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets UCL Volts trap repeat rate in seconds"
    ::= { pduTrapPerEntry 3 }

pduRMSVoltsUWLTrapPer  OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets UWL Volts trap repeat rate in seconds"
    ::= { pduTrapPerEntry 4 }

pduRMSVoltsLWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets LWL Volts trap repeat rate in seconds"
    ::= { pduTrapPerEntry 5 }

pduRMSVoltsLCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets LCL Volts trap repeat rate in seconds"
    ::= { pduTrapPerEntry 6 }

pduRMSAmpsUCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets UCL current trap repeat rate in seconds"
    ::= { pduTrapPerEntry 7 }

pduRMSAmpsUWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets UWL current trap repeat rate in seconds"
    ::= { pduTrapPerEntry 8 }

pduRMSAmpsLWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets LWL current trap repeat rate in seconds"
    ::= { pduTrapPerEntry 9 }

pduRMSAmpsLCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets LCL current trap repeat rate in seconds"
    ::= { pduTrapPerEntry 10 }

pduEnergyUCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets UCL total energy trap repeat rate in seconds"
    ::= { pduTrapPerEntry 11 }

pduEnergyUWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets UWL total energy trap repeat rate in seconds"
    ::= { pduTrapPerEntry 12 }

pduMeanKVAUCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean kVA UCL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 13 }

pduMeanKVAUWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean kVA UWL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 14 }

pduMeanKVALWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean kVA LWL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 15 }

pduMeanKVALCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean kVA LCL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 16 }

pduMeanKWattsUCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean power UCL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 17 }

pduMeanKWattsUWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean power UWL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 18 }

pduMeanKWattsLWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean power LWL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 19 }

pduMeanKWattsLCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets mean power LCL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 20 }

pduPwrFactorUCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets power factor UCL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 21 }

pduPwrFactorUWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets power factor UWL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 22 }

pduPwrFactorLWLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets power factor LWL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 23 }

pduPwrFactorLCLTrapPer	OBJECT-TYPE
    SYNTAX    INTEGER (30..32000)
    MAX-ACCESS    read-write
    STATUS    current
    DESCRIPTION
        "Sets power factor LCL trap repeat rate in seconds"
    ::= { pduTrapPerEntry 24 }

-- }}} End of pduTrapPerTable

-- }}} End of pduMonitor group
-- {{{ pdus traps

-- To Be Added

-- {{{ pdus RMS Volt traps

-- To Be Added

-- }}} End of pdus RMS Volt traps
-- {{{ pdus RMS Amp traps

-- To Be Added

-- }}} End of pdus RMS Amp traps
-- {{{ pdus Total Energy traps

-- To Be Added

-- }}} End of pdus Total Energy traps

-- }}} End of pdus traps

-- }}} End of pdus group
-- {{{ inventory group

invProdSignature  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..7))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Product data signature."
	::= { inventory 1 }

invProdFormatVer  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..7))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Product data format version."
	::= { inventory 2 }

invManufCode  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Manufacturer code."
	::= { inventory 3 }

invOrderNum  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..7))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Order number."
	::= { inventory 4 }

invBatchNum  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..7))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Batch number."
	::= { inventory 5 }

invProdTestTime  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Data and time of production test."
	::= { inventory 6 }

invUnitName  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Unit name."
	::= { inventory 7 }

invUnitPartNum  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..31))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Unit part number."
	::= { inventory 8 }

invHwRevision  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..31))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Hardware revision number."
	::= { inventory 9 }

invFwRevision  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Firmware revision number."
	::= { inventory 10 }

invSerialNum  OBJECT-TYPE
	SYNTAX      DisplayString (SIZE(0..15))
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Serial number."
	::= { inventory 11 }

invDefaultIPAddrType  OBJECT-TYPE
	SYNTAX      InetAddressType
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"The type of the IP addresses."
	::= { inventory 12 }

invDefaultIPAddr  OBJECT-TYPE
	SYNTAX      InetAddress
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Default unit IP address."
	::= { inventory 13 }

invDefaultSubNetMask  OBJECT-TYPE
	SYNTAX      InetAddress
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Default unit sub-network mask."
	::= { inventory 14 }

invDefaultGWAddr  OBJECT-TYPE
	SYNTAX      InetAddress
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Default unit default gateway address."
	::= { inventory 15 }

invMacAddr  OBJECT-TYPE
	SYNTAX      MacAddress
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Unit medium access control (MAC) address."
	::= { inventory 16 }

invOk  OBJECT-TYPE
	SYNTAX      TruthValue
	MAX-ACCESS  read-only
	STATUS      current
	DESCRIPTION
		"Confirms that the inventory record isn't corrupted."
	::= { inventory 20 }

invInputCount	OBJECT-TYPE
	SYNTAX		INTEGER   (0..24)
    MAX-ACCESS  read-only
    STATUS    	current
    DESCRIPTION
        "The maximum number of inputs that can be connected to the unit"
    ::= { inventory 50 }	
    
invOutputCount	OBJECT-TYPE
	SYNTAX		INTEGER (0..24)   
    MAX-ACCESS  read-only
    STATUS    	current
    DESCRIPTION
        "The maximum number of outputs that can be connected to the unit"
    ::= { inventory 51 }
    
invKeypadCount	OBJECT-TYPE
	SYNTAX		INTEGER (0..2)
    MAX-ACCESS  read-only
    STATUS    	current
    DESCRIPTION
        "The maximum number of keypads that can be connected to the unit"    
    ::= { inventory 52 }	
    
invAcuCount	OBJECT-TYPE
	SYNTAX		INTEGER (0..6)
    MAX-ACCESS  read-only
    STATUS    	current
    DESCRIPTION
        "The maximum number of ACU's that can be connected to the unit"
    ::= { inventory 53 }	
    
invAccessUserCount	OBJECT-TYPE
	SYNTAX		INTEGER (0..20)
    MAX-ACCESS  read-only
    STATUS    	current
    DESCRIPTION
        "The maximum number of user entries on the unit"
    ::= { inventory 54 }	        
    
invPduCount	OBJECT-TYPE
	SYNTAX		INTEGER (0..6)
    MAX-ACCESS  read-only
    STATUS    	current
    DESCRIPTION
        "The maximum number of PDU's that can be connected to the unit"
    ::= { inventory 55 }	    

-- }}} End of inventory group
-- {{{ trapInfo group

trapCode OBJECT-TYPE
	SYNTAX Unsigned32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A decimal number to be carried on notifications of types 1 to 4 identifying the event which caused it. 
		The format of this number is BBEEffCCT where

			BB is the number of the relevant MIB branch.
 			EE indicates what type of event caused the notification. This value is dependent upon branch number and implementation.
			CC is the channel number which was the source of the notification.
			T discriminates the type of data, e.g. temperature. This value is dependent upon branch number and implementation.
			ff future use.

			Fields are packed with leading zeros and are set to zero if not relevant to a particular notification."
	::= { trapInfo 1 }

trapDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..63))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A string to be carried on notifications of types 1 to 4 identifying the event which caused it. 
		The format of this string is as follows.
			Field 1 - type of notification, e.g. warning, critical, etc.
			Field 2 - data source, e.g. inputs. Generally this relates to a particular MIB branch.
			Field 3 - channel number, e.g. input 1.
			Field 4 - event, i.e. what caused the trap.
			Field 5 - value at which the event occured, e.g. 900, indicating 90% humidity.
			Field 6 - type of data, e.g. relative humidity
			
		Fields are omitted if not relevant to a particular notification."
	::= { trapInfo 2 }
            
-- }}} End of trapInfo group

-- {{{ Generic traps

alarmCritical NOTIFICATION-TYPE
	OBJECTS  { trapCode, trapDescription }
    STATUS      current
	DESCRIPTION
		"Critical alarm."
	::= { traps 1 }

alarmWarning NOTIFICATION-TYPE
	OBJECTS  { trapCode, trapDescription }
    STATUS      current
	DESCRIPTION
		"Warning alarm."
	::= { traps 2 }

alarmInformation NOTIFICATION-TYPE
	OBJECTS  { trapCode, trapDescription }
    STATUS      current
	DESCRIPTION
		"Information alarm."
	::= { traps 3 }

alarmCleared NOTIFICATION-TYPE
	OBJECTS  { trapCode, trapDescription }
    STATUS      current
	DESCRIPTION
		"Alarm cleared."
	::= { traps 4 }

-- }}} End of Generic traps        

END